Vermont Watershed Management in DEC at ANR


Newly Reported Overflow
Facility Name:
Facility Number:
PermitID:
Submission Number: HN3-DM1C-C0R68
Current Status: Deemed Complete
SubVersionID: 738768d2-0b33-4458-bdce-9781abcf5366
Location: 39 Cascade Street Wastewater Facility
Caller Name And Title: James Jutras, Water Quality Supt. Chief Operator
Incident Start Date: 3/16/2017 4:00:00 AM
Incident End Date: 3/16/2017 4:00:00 AM
Contact Name And Title For Public: James Jutras, Water Quality Supt, Chief Operator
Public Contact Phone Number: 802-878-6943 ext 101
Incident Start Time: 06:15 pm
Incident End Time: 09:10 pm
Estimated Volume: 100,000 to 500,000 gallons
Nature Of Incident: Discharged treated and partially disinfected effluent
Cause Of Discharge: Other - Please describe in Description of Incident
Type Of Obstruction: N/A
Point Of Discharge: WWTF outfall
Corrective Action Taken: made process adjustments, increased chemical feed set point and increased the rate of adjustment for automated feed systems.
Waterbody Impacted: Winooski River
Description Of Incident: High Chemical Demand caused under disinfection of fully treated final effluent. E. Coli analysis 437 Colonies/100 ml at 0.49 mg/L total chlorine residual