Waste Water Inventory Website
            Watershed Management Website Drinking Water Website Waste Management Website
View FacilityIncident Record


Facility Name: Whitingham    
Christopher Hayes operator    
Whitingham    
outfall wwtf-Harriman reservoir    
04/08/2024    
04/23/2023    
10:00 am to 02:17 pm    
   
Discharged treated and partly disinfected effluent    
>1,000 to 10,000 gallons    
Other    
   
WWTF outfall    
Increased water level in influent tank and raised the pump up to a higher level to prevent solids from passing through the pump. Decrease the frequency of pump relocation. Suggested changing the temporary pump to a smaller gpm. Lowered gpm cleaned effluent piping, cleaned UVs. now 52 count    
Harriman Reservoir    
Christopher Hayes    
   
   
nForms    
Y    
   
   
   
Plant under construction, running on temporary pump. Pump set too low in influent tank #1. E-coli level too high. Temporary Pump location is being changed to accommodate construction from tank to tank.    
   
HQ2-T26H-KEQQ4