|
Facility Name:
|
Montpelier
|
|
|
Christopher Cox - Chief Operator
|
|
|
City of Montpelier
|
|
|
CSO 003 Bailey Ave
|
|
|
07/15/2024
|
|
|
07/16/2024
|
|
|
11:35 am to 07:25 am
|
|
|
|
|
|
Discharged untreated sewage
|
|
|
10000
|
|
|
Obstruction/Blockage
|
|
|
CSO Monitoring Equipment
|
|
|
Combined sewer overflow structure
|
|
|
Cleaned line with a vactor and removed velocity sensor from pipe. Then put in a work order with the CSO monitor company to send out a technician to install a new velocity sensor.
|
|
|
Winooski River
|
|
|
Kurt Motyka - Public Works Director
|
|
|
|
|
|
|
|
|
nForms
|
|
|
Y
|
|
|
|
|
|
|
|
|
|
|
|
A velocity sensor that is mounted in the sewer line for the CSO monitoring equipment at location CSO 003 - Bailey Ave became unfixed and created a partial blocked on 7/15/24. This blockage caused the sewer line to overflow into the CSO structure. Most likely the sensor mounting brackets were compromised during the flooding event the prior week (7/10/24).
|
|
|
|
|
|
HQ5-5HCK-9RMMK
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|