Facility Name:
|
Plainfield
|
|
|
Greg Chamberlin, Chief Operator
|
|
|
Plainfield
|
|
|
Wastewater Treatment Plant
|
|
|
09/01/2021
|
|
|
09/02/2021
|
|
|
09:00 am to 02:30 pm
|
|
|
|
|
|
Discharged treated and partly disinfected effluent
|
|
|
>10,000 to 100,000 gallons
|
|
|
Other
|
|
|
|
|
|
WWTF outfall
|
|
|
Flushed UV channel to clean lamps. Slowed the transfer of material between SBR #2 to SBR #1 to prevent overloading. Sample was sent to lab to verify that disinfection is effective. Results of lab show <10 MPN/100 mL. Notices were posted to inform the community of the violation. The town Health Officer placed the notices. We have cleaned the UV channels of debris.
|
|
|
Winooski River
|
|
|
Greg Chamberlin, Chief Operator
|
|
|
|
|
|
|
|
|
nForms
|
|
|
Y
|
|
|
|
|
|
|
|
|
|
|
|
Transferring wastewater from SBR #2 to SBR #1 to clear debris in bottom of tank. Transferred too quickly and overloaded the tank not allowing for sufficient settling to occur before decant. UV lamp system not able to fully disinfect.
|
|
|
|
|
|
HPB-EZ6T-K2ZS3
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|