View FacilityIncident Record


Facility Name: Newport City    
Pedro Grondin operator    
City of newport    
Indian Head pump station    
06/16/2021    
06/16/2021    
11:00 am to 12:00 pm    
   
Discharged untreated sewage    
>1,000 to 10,000 gallons    
Mechanical Failure    
none    
Other    
found power supply to controller had failed and shut controller down electrician replace power supply and controller was up and running while getting system back on line found controller had a low wet well level on same day at 10:28 AM i arrived at 11:45 AM on further investigating we found that the transducer and low level floats had failed the float had shorted out and was the cause of power supply to fail replaced float with new float and replaced transducer with Vega radar unit this units are not in wastewater they are above making it a better device for this station we have in the past had problems with transducer in this station 3/4 of the flow to this station is from Indian head manufacturing from there vats that they soak there logs in most of the flow is clean water that is from 140 degrees to 180 degrees which shortens the life of transducers 5 years ago we up grade to a higher temp transducer which last longer than one in the past . After all parts were replace station was back to normal and no problems    
wetlands behind pumpstation    
Thomas Bernier Public works director    
   
   
nForms    
Y    
   
   
   
Was called to pump station found had high level in wet well check pumps found pumps found controller was trip out and pumps were off but pumps in hand and found would run but were air bound bleed pumps and pumps started pumping on hand and pumped wet well down so ran on hand while investigating what happened to controller    
   
HP9-JA1P-JD7YK