Facility Name:
|
Milton
|
|
|
Thomas Elwood Superintendent
|
|
|
Town of Milton
|
|
|
145 Lamoille Terrace WWTF outfall
|
|
|
02/17/2022
|
|
|
02/17/2022
|
|
|
12:10 pm to 01:15 pm
|
|
|
|
|
|
Discharged partly treated undisinfected effluent
|
|
|
>100,000 to 500,000 gallons
|
|
|
Other
|
|
|
High turbidity, and attached growth on b
|
|
|
WWTF outfall
|
|
|
preformed site survey for reasons for E-coli to be high. finding no obvious reason except for elevated turbidity (3.64ntu online turbidity meter) we have resampled and are awaiting results. Did bulb end and channel cleaning, changed a couple of burnt/broken bulbs and resampled.
|
|
|
Lamoille
|
|
|
Thomas Elwood Superintendent Water/Wastewater
|
|
|
|
|
|
|
|
|
nForms
|
|
|
Y
|
|
|
|
|
|
|
|
|
|
|
|
High e-coli value reported from Endyne Labs 870 on 2/17/22 @12:10 pm from sample taken on 2/16/22@11:04. resampled on 2/17/22 @1:15 PM result was 319 (high but below permit level). resampled after cleaning and changing couple of burnt out bulbs on 2/18/21 @10:45 result was 125.
|
|
|
|
|
|
HPF-J7SM-J4JMW
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|