Facility Name: Fair Haven    
Peter Laramie, Chief Operator    
Fair Haven    
Fair Haven WWTF    
07/15/2018    
07/16/2018    
01:00 pm to 05:35 am    
   
Discharged treated and partly disinfected effluent    
>10,000 to 20,000 gallons    
Chem Feed Problem    
   
WWTF outfall    
I pumped off a quantity of hypochlorite and liberally disbursed that by hand throughout the chlorine contact tank beginning at the end. I then replaced the internal tubing of the peristaltic pump and ran the pump on high speed for several minutes until the chemical was reaching the contact tank. The entire process took about 15 minutes.    
Castleton River    
Peter Laramie    
   
   
nForms    
Y    
   
   
   
Late morning/early afternoon 7/15/2018 the hypochlorite pump stopped taking up chemical, but continued to discharge the chemical in the discharge line for at least two hours. Due to very low flows the treated but partially disinfected and partially undisinfected wastewater was still in the large chlorine contact tank when I found the problem at 5:22 a.m. on 7/16.    
   