Facility Name: Fair Haven    
Peter Laramie, Chief Operator    
Fair Haven    
Adams Street Pump Station    
02/04/2016    
02/04/2016    
07:00 pm to 09:30 pm    
   
Discharged untreated sewage    
>1,000 to 10,000 gallons    
Other    
   
Pump station emergency overflow pipe    
An assistant chief operator was called to the pump station and arrived shortly before 9:30 p.m. He determined that when one of the pumps was called for it disabled both pumps. He turned off that one pump and used the other pump exclusively to end the overflow and operate the pump station. Since then the new relay has been removed and bypassed again until the cause of the malfunction can be diagnosed and corrected    
Castleton River    
Peter Laramie, Chief Operator Fair Haven WWTF    
   
   
nForms    
Y    
   
   
   
The cause of the incident is still under investigation by plant personnel, but the problem was apparently caused by a malfunction of the pump controller. A technician determined that a malfunctioning relay was causing a problem on 2/1/2016. The relay was removed and bypassed until a new relay could be installed. The new relay was installed at 10 a.m. on 2/04/2016, nine hours prior to the malfunction which caused the overflow. The length of the overflow was prolonged because the operators were out of the area or otherwise out of telephone dialer contact until 9:15 p.m.    
   