Facility Name:
|
Fairfax
|
|
|
Amy Sears- Utility Manager
|
|
|
Town of Fairfax
|
|
|
142 Hunt Street
|
|
|
03/08/2022
|
|
|
03/29/2022
|
|
|
10:30 am to 10:42 am
|
|
|
|
|
|
Discharged treated and partly disinfected effluent
|
|
|
>100,000 to 500,000 gallons
|
|
|
Other
|
|
|
none
|
|
|
WWTF outfall
|
|
|
We increased the rate of chlorine to the contact chamber flow rate.
|
|
|
LaMoille River
|
|
|
Randy DeVine- Chief Waste Water Operator
|
|
|
|
|
|
|
|
|
nForms
|
|
|
Y
|
|
|
|
|
|
|
|
|
|
|
|
Effluent discharge flows increased due to snow melting and other situations in the system. Upon knowing the chlorine residuals on this day of sampling, we observed a low chlorine residual at EFF outfall. Upon being alerted we increased our chlorine residuals, which in turn should have had enough time for chlorine contact to get us a good kill on E-Coli.
Test #1 sample date 3-8-22 Analysis time 17:40 500 cfu TRC value .51
Test #2 sample date 3-15-22 Analysis time 16:10 470 cfu TRC value 1.03
Test #3 sample date 3-24-22 Analysis time 17:45 <10 cfu TRC value .92
|
|
|
|
|
|
HPG-5XK9-G5B3M
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|