Facility Name:
|
Chelsea
|
|
|
Mike Whipple cheif operator
|
|
|
chelsea
|
|
|
outfall of waste water treatment plant
|
|
|
06/03/2025
|
|
|
06/04/2025
|
|
|
01:55 pm to 11:20 am
|
|
|
|
|
|
Discharged partially treated disinfected effluent
|
|
|
27000
|
|
|
Chem Feed Problem
|
|
|
|
|
|
WWTF outfall
|
|
|
increased pump rate and mixed up fresh chlorine solution
|
|
|
first branch of white river
|
|
|
mike whipple chief operator
|
|
|
|
|
|
|
|
|
nForms
|
|
|
Y
|
|
|
|
|
|
|
|
|
|
|
|
low chlorine residual do to increasing air temp and low pump application rate. The failed E.coli sample was taken at 1:55pm on 6/3/25 and the TRC was 0.27. The second E.coli sample was taken at 11:20am on 6/4/25 and had a TRC of 0.52. The second sample had a result of <1. The total amount discharge during this period was roughly 27000 gallons.
|
|
|
|
|
|
HQD-3FVF-BZYJX
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|