Facility Name:
|
Chelsea
|
Caller Name And Title:
|
Mike Whipple cheif operator
|
Municipality:
|
chelsea
|
Location (street or site):
|
outfall of waste water treatment plant
|
Incident Start Date:
|
06/03/2025
|
Incident End Date:
|
06/04/2025
|
Incident Start End Times:
|
01:55 pm to 11:20 am
|
Estimated Duration Of Event:
|
|
Nature Of Incident:
|
Discharged partially treated disinfected effluent
|
Estimated Volume (gallons):
|
27000
|
Cause Of Discharge:
|
Chem Feed Problem
|
Type Of Obstruction:
|
|
Point Of Discharge:
|
WWTF outfall
|
Corrective Action Taken:
|
increased pump rate and mixed up fresh chlorine solution
|
Waterbody Impacted:
|
first branch of white river
|
Contact Name And Title For Public:
|
mike whipple chief operator
|
Call Date:
|
|
WW Staff Called:
|
|
Type Of Notification:
|
nForms
|
Public Overflow Report For Web:
|
Y
|
|
|
|
|
|
|
Description Of Incident:
|
low chlorine residual do to increasing air temp and low pump application rate. The failed E.coli sample was taken at 1:55pm on 6/3/25 and the TRC was 0.27. The second E.coli sample was taken at 11:20am on 6/4/25 and had a TRC of 0.52. The second sample had a result of <1. The total amount discharge during this period was roughly 27000 gallons.
|
|
|
nForm Submission Number:
|
HQD-3FVF-BZYJX
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|