Waste Water Inventory Website
            Watershed Management Website Drinking Water Website Waste Management Website
View FacilityIncident Record


Facility Name: Chelsea    
Mike Whipple cheif operator    
chelsea    
outfall of waste water treatment plant    
06/03/2025    
06/04/2025    
01:55 pm to 11:20 am    
   
Discharged partially treated disinfected effluent    
27000    
Chem Feed Problem    
   
WWTF outfall    
increased pump rate and mixed up fresh chlorine solution    
first branch of white river    
mike whipple chief operator    
   
   
nForms    
Y    
   
   
   
low chlorine residual do to increasing air temp and low pump application rate. The failed E.coli sample was taken at 1:55pm on 6/3/25 and the TRC was 0.27. The second E.coli sample was taken at 11:20am on 6/4/25 and had a TRC of 0.52. The second sample had a result of <1. The total amount discharge during this period was roughly 27000 gallons.    
   
HQD-3FVF-BZYJX