Facility Name:
|
Brandon
|
Caller Name And Title:
|
Stephen Cijka Chief Operator
|
Municipality:
|
Town of Brandon
|
Location (street or site):
|
Wastewater Plant Outfall
|
Incident Start Date:
|
08/09/2018
|
Incident End Date:
|
08/10/2018
|
Incident Start End Times:
|
07:30 am to 01:50 pm
|
Estimated Duration Of Event:
|
|
Nature Of Incident:
|
Discharged partially treated disinfected effluent
|
Estimated Volume (gallons):
|
>100,000 to 500,000 gallons
|
Cause Of Discharge:
|
Chem Feed Problem
|
Type Of Obstruction:
|
|
Point Of Discharge:
|
WWTF outfall
|
Corrective Action Taken:
|
Turned up chemical feed pump speed and e mail instrumentation man to check out the 4-20 milliamp signal that drives the chemical feed pumps
|
Waterbody Impacted:
|
Neshobe River
|
Contact Name And Title For Public:
|
Dave Atherton Town Manager
|
Call Date:
|
|
WW Staff Called:
|
|
Type Of Notification:
|
nForms
|
Public Overflow Report For Web:
|
Y
|
|
|
|
|
|
|
Description Of Incident:
|
Apparently the chlorine contact chamber's residual of 1.57 mg/l was not enough to kill enough bacteria meet the 77/100ml e coli limit. The e coli reading was 98/100ml.
|
|
|
nForm Submission Number:
|
HNF-Z1SM-2GR2Z
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|