Facility Name:
|
Bethel
|
|
Caller Name And Title:
|
Richard Manning Chief Operator
|
|
Municipality:
|
Town of Bethel
|
|
Location (street or site):
|
WWTP Outfall Lat. 43.82373 Long. -72.62254
|
|
Incident Start Date:
|
01/28/2026
|
|
Incident End Date:
|
02/02/2026
|
|
Incident Start End Times:
|
06:00 am to 09:30 am
|
|
Estimated Duration Of Event:
|
|
|
Nature Of Incident:
|
Discharged partly treated undisinfected effluent
|
|
Estimated Volume (gallons):
|
209000
|
|
Cause Of Discharge:
|
Other
|
|
Type Of Obstruction:
|
E Coli `permit exceedance
|
|
Point Of Discharge:
|
WWTF outfall
|
|
Corrective Action Taken:
|
Working on recovery from toxicity causing biological upset.
|
|
Waterbody Impacted:
|
White River
|
|
Contact Name And Title For Public:
|
Richard Manning
|
|
Call Date:
|
|
|
WW Staff Called:
|
|
|
Type Of Notification:
|
nForms
|
|
Public Overflow Report For Web:
|
Y
|
|
|
|
|
|
|
|
|
|
|
Description Of Incident:
|
Believed toxicity caused a Biological upset with flock formers, causing turbidity. Turbid effluent in turn affecting light transmission and UV effectiveness, causing ineffective treatment for E Coli. From 1/28/26 to 2/2/26 we calculated based upon daily flows that approximately 209,000 gallons of effluent was discharged exceeding our permit limit for E Coli. As of 2/2/26 we are back in compliance with our E Coli limits, but still experiencing some turbidity while we still fully recover from this upset.
|
|
|
|
|
nForm Submission Number:
|
HQJ-Z8SJ-TKZ22
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|