Facility Name: Bethel    
Richard Manning Chief Operator    
Town of Bethel    
WWTP Outfall Lat. 43.82373 Long. -72.62254    
01/28/2026    
02/02/2026    
06:00 am to 09:30 am    
   
Discharged partly treated undisinfected effluent    
209000    
Other    
E Coli `permit exceedance    
WWTF outfall    
Working on recovery from toxicity causing biological upset.    
White River    
Richard Manning    
   
   
nForms    
Y    
   
   
   
Believed toxicity caused a Biological upset with flock formers, causing turbidity. Turbid effluent in turn affecting light transmission and UV effectiveness, causing ineffective treatment for E Coli. From 1/28/26 to 2/2/26 we calculated based upon daily flows that approximately 209,000 gallons of effluent was discharged exceeding our permit limit for E Coli. As of 2/2/26 we are back in compliance with our E Coli limits, but still experiencing some turbidity while we still fully recover from this upset.    
   