Facility Name:
|
Brighton
|
|
Caller Name And Title:
|
Kean Galunas Chief Operator
|
|
Municipality:
|
Brighton
|
|
Location (street or site):
|
Brighton WWTF outfall
|
|
Incident Start Date:
|
04/16/2026
|
|
Incident End Date:
|
04/22/2026
|
|
Incident Start End Times:
|
08:52 am to 07:30 am
|
|
Estimated Duration Of Event:
|
|
|
Nature Of Incident:
|
Discharged treated and partly disinfected effluent
|
|
Estimated Volume (gallons):
|
416000
|
|
Cause Of Discharge:
|
Other
|
|
Type Of Obstruction:
|
|
|
Point Of Discharge:
|
WWTF outfall
|
|
Corrective Action Taken:
|
Flow was temporarily reduced to a level that was previously providing adequate treatment and then increased by a smaller rate than was first attempted. Chlorination rate was also increased, and this combination brought the e. coli measurement below the public notification level. (Note: Total volume is necessarily calculated as the flow measured between the initial and follow up e. coli tests and may not represent the true duration of the event.)
|
|
Waterbody Impacted:
|
Pherrins River
|
|
Contact Name And Title For Public:
|
Kean Galunas Chief Operator
|
|
Call Date:
|
|
|
WW Staff Called:
|
|
|
Type Of Notification:
|
nForms
|
|
Public Overflow Report For Web:
|
Y
|
|
|
|
|
|
|
|
|
|
|
Description Of Incident:
|
An increase in the effluent pumping rate to draw down the lagoons for construction work reduced the detention time in the chlorine contact tank. The chlorine residual of .93 mg/l proved inadequate for effective disinfection, with an e. coli test result of 248.1 MPN/100mL.
Public notification is required for results above 235.
|
|
|
|
|
nForm Submission Number:
|
HQM-WPJB-XP8ZP
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|