Waste Water Inventory Website
            Watershed Management Website Drinking Water Website Waste Management Website
View FacilityIncident Record


Facility Name: Brighton    
Kean Galunas Chief Operator    
Brighton    
Brighton WWTF outfall    
04/16/2026    
04/22/2026    
08:52 am to 07:30 am    
   
Discharged treated and partly disinfected effluent    
416000    
Other    
   
WWTF outfall    
Flow was temporarily reduced to a level that was previously providing adequate treatment and then increased by a smaller rate than was first attempted. Chlorination rate was also increased, and this combination brought the e. coli measurement below the public notification level. (Note: Total volume is necessarily calculated as the flow measured between the initial and follow up e. coli tests and may not represent the true duration of the event.)    
Pherrins River    
Kean Galunas Chief Operator    
   
   
nForms    
Y    
   
   
   
An increase in the effluent pumping rate to draw down the lagoons for construction work reduced the detention time in the chlorine contact tank. The chlorine residual of .93 mg/l proved inadequate for effective disinfection, with an e. coli test result of 248.1 MPN/100mL. Public notification is required for results above 235.    
   