Waste Water Inventory Website
            Watershed Management Website Drinking Water Website Waste Management Website
View FacilityIncident Record


Facility Name: Brighton    
Kean Galunas Chief Operator    
Brighton    
Pherrins River    
09/03/2025    
   
   
   
Discharged treated and partly disinfected effluent    
88000    
Other    
   
WWTF outfall    
Pump placement is being evaluated, and chlorination is being increased.    
Pherrins River    
Kean Galunas Chief Operator    
   
   
nForms    
Y    
   
   
   
Finding an optimal placement for the lagoon dewatering pump is proving difficult at the current low water level in the lagoon. Catching up with increasing chlorine demand is also hindering effective chlorination. Combined, these led to an e. coli test result of 290 MPN/100 ml which is over the 235 public notification threshold.    
   
HQF-BW35-9TZH9