Facility Name:
|
Brighton
|
|
|
Kean Galunas Chief Operator
|
|
|
Brighton
|
|
|
Outfall
|
|
|
04/02/2025
|
|
|
04/16/2025
|
|
|
07:20 am to 07:14 am
|
|
|
|
|
|
Discharged treated and partly disinfected effluent
|
|
|
1537000
|
|
|
Other
|
|
|
|
|
|
WWTF outfall
|
|
|
The chlorination rate was increased, and a follow up e. coli test was performed on 09 Apr.
That result was 240 MPN/100 ml, which was still over the 235 public notification level. Another sample taken on 16 Apr had a result of 21 MPN/100 ml, allowing this notification to be closed.
|
|
|
Pherrins River / Clyde River
|
|
|
Kean Galunas Chief Operator
|
|
|
|
|
|
|
|
|
nForms
|
|
|
Y
|
|
|
|
|
|
|
|
|
|
|
|
Recent rains and spring runoff reduced detention time in the chlorine contact tank, hindering efforts to achieve adequate disinfection. An e. coli test conducted on 02 Apr showed a result of 1100 MPN/100 ml, triggering public notification.
|
|
|
|
|
|
HQB-JTJ4-JWT1V
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|