Facility Name:
|
Shelburne 1 (Crown Rd)
|
|
|
Walt Arsenault, Chief Operator WWTF 1
|
|
|
Shelburne
|
|
|
Wastewater Facility 1
|
|
|
10/19/2022
|
|
|
10/19/2022
|
|
|
08:00 am to 10:00 am
|
|
|
|
|
|
Discharged treated and partly disinfected effluent
|
|
|
>10,000 to 100,000 gallons
|
|
|
Unknown
|
|
|
|
|
|
WWTF outfall
|
|
|
Increased chlorine distribution for decants.
|
|
|
Shelburne Bay
|
|
|
Walt Arsenault
|
|
|
|
|
|
|
|
|
nForms
|
|
|
Y
|
|
|
|
|
|
|
|
|
|
|
|
Was notified on 21 Oct 22 that E-coli sample captured on 19 Oct 22 failed with over 800 colonies. However, the chlorine residual for that decant/sample was 2.13 mg/l and plant issued 12.5 gallons of chlorine for that 24 hour period. Turbidity was a low 1.26 NTUs and looked very clear. With local level sample results, it's difficult to understand why or how Plant 1 failed with an E-coli sample that high.
|
|
|
|
|
|
HPN-KBXH-J1KQT
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|