Waste Water Inventory Website
            Watershed Management Website Drinking Water Website Waste Management Website
View FacilityIncident Record


Facility Name: Windsor Main    
Harry Benner    
Windsor,Vt    
Main Plant Effluent    
11/06/2025    
11/08/2025    
09:00 am to 02:00 pm    
   
Discharged partially treated disinfected effluent    
400000    
Chem Feed Problem    
none    
WWTF outfall    
Repaired chorine analyzer and also cleaned chlorine contact chamber.    
Connecticut River    
Harry Benner    
   
   
nForms    
Y    
   
   
   
We had a problem with our chem feed pump at 7am Nov. 6 2025 . At approximately 9am with a total chlorine residual of 1.36ppm we collected the sample for e-coli. However the result came in at 2400 MPN/100 ml. Retook sample at 11:30am on Nov. 7,2025 and delivered to Endyne labs for analysis.. The test result on that sample was 2MPN/100ml.    
   
HQG-Y3T4-M6NG5