Waste Water Inventory Website
            Watershed Management Website Drinking Water Website Waste Management Website
View FacilityIncident Record

Skip Navigation Links

Facility Name: Windsor Main    
Caller Name And Title: Harry Benner    
Municipality: Windsor,Vt    
Location (street or site): Main Plant Effluent    
Incident Start Date: 11/06/2025    
Incident End Date: 11/08/2025    
Incident Start End Times: 09:00 am to 02:00 pm    
Estimated Duration Of Event:    
Nature Of Incident: Discharged partially treated disinfected effluent    
Estimated Volume (gallons): 400000    
Cause Of Discharge: Chem Feed Problem    
Type Of Obstruction: none    
Point Of Discharge: WWTF outfall    
Corrective Action Taken: Repaired chorine analyzer and also cleaned chlorine contact chamber.    
Waterbody Impacted: Connecticut River    
Contact Name And Title For Public: Harry Benner    
Call Date:    
WW Staff Called:    
Type Of Notification: nForms    
Public Overflow Report For Web: Y    
   
   
   
Description Of Incident: We had a problem with our chem feed pump at 7am Nov. 6 2025 . At approximately 9am with a total chlorine residual of 1.36ppm we collected the sample for e-coli. However the result came in at 2400 MPN/100 ml. Retook sample at 11:30am on Nov. 7,2025 and delivered to Endyne labs for analysis.. The test result on that sample was 2MPN/100ml.    
   
nForm Submission Number: HQG-Y3T4-M6NG5