Facility Name:
|
Windsor Main
|
|
Caller Name And Title:
|
Harry Benner
|
|
Municipality:
|
Windsor,Vt
|
|
Location (street or site):
|
Main Plant Effluent
|
|
Incident Start Date:
|
11/06/2025
|
|
Incident End Date:
|
11/08/2025
|
|
Incident Start End Times:
|
09:00 am to 02:00 pm
|
|
Estimated Duration Of Event:
|
|
|
Nature Of Incident:
|
Discharged partially treated disinfected effluent
|
|
Estimated Volume (gallons):
|
400000
|
|
Cause Of Discharge:
|
Chem Feed Problem
|
|
Type Of Obstruction:
|
none
|
|
Point Of Discharge:
|
WWTF outfall
|
|
Corrective Action Taken:
|
Repaired chorine analyzer and also cleaned chlorine contact chamber.
|
|
Waterbody Impacted:
|
Connecticut River
|
|
Contact Name And Title For Public:
|
Harry Benner
|
|
Call Date:
|
|
|
WW Staff Called:
|
|
|
Type Of Notification:
|
nForms
|
|
Public Overflow Report For Web:
|
Y
|
|
|
|
|
|
|
|
|
|
|
Description Of Incident:
|
We had a problem with our chem feed pump at 7am Nov. 6 2025 . At approximately 9am with a total chlorine residual of 1.36ppm we collected the sample for e-coli. However the result came in at 2400 MPN/100 ml. Retook sample at 11:30am on Nov. 7,2025 and delivered to Endyne labs for analysis.. The test result on that sample was 2MPN/100ml.
|
|
|
|
|
nForm Submission Number:
|
HQG-Y3T4-M6NG5
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|