Waste Water Inventory Website
            Watershed Management Website Drinking Water Website Waste Management Website
View FacilityIncident Record


Facility Name: Windsor Main    
Harry Benner Assistant Chief Operator    
Town of Windsor    
Main Plant    
11/07/2019    
11/12/2019    
07:30 am to 01:45 pm    
   
Other    
bad sample collection    
Other    
none    
WWTF outfall    
We are now taking the E coli sample at the effluent weir but on the upside of it just before the effluent goes over it.    
Connecticut river    
Harry Benner    
   
   
nForms    
Y    
   
   
   
On Nov 7, 2019 we had an E coli result of 360 per100mls and on the following day a result of 96 per 100mls. We then suspected that the sample was being contaminated by algae coming off the eff weir. the next sample taken on Nov 12 and was taken before the weir and the result was 5 per 100mls.    
   
HNV-4DEV-W4XMA