Facility Name:
|
St Albans City
|
|
|
Brian Willett
|
|
|
City of St.albans
|
|
|
At the main wastewater plant
|
|
|
08/11/2024
|
|
|
08/11/2024
|
|
|
03:50 pm to 05:30 pm
|
|
|
|
|
|
Discharged treated and partly disinfected effluent
|
|
|
168000
|
|
|
Other
|
|
|
|
|
|
WWTF outfall
|
|
|
The milk spill caused the Chlorine demand to go up which set off an alarm for Low Cl2 residual. This caused a E coli violation on the final. An E coli test was not done but with the low residual there would have been an violation. When I came in for the alarm and when I figured out what was going on I increased The Sodium Hypochlorite feed rate to feed more Hypochlorite to bring the residual back up to put us back in compliance
|
|
|
Stevens Brook Lake champlain
|
|
|
Marty Manahan Director of Public Works
|
|
|
|
|
|
|
|
|
nForms
|
|
|
Y
|
|
|
|
|
|
|
|
|
|
|
|
A local Creamery had a milk spill that discharged to the city sewer that goes to the plant. This caused The Chlorine demand to go up which caused a E coli violation on the final Effluent for approximately 1.5 hrs.
|
|
|
|
|
|
HQ5-TRMN-J776D
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|