Waste Water Inventory Website
            Watershed Management Website Drinking Water Website Waste Management Website
View FacilityIncident Record


Facility Name: St Albans City    
Brian Willett Chief Operator    
City of St.Albans    
the main Wastewater plant    
12/18/2023    
12/19/2023    
08:28 am to 09:30 am    
   
Discharged partially treated disinfected effluent    
>1,000,000 gallons    
High Flows    
   
WWTF outfall    
At the time the test was done we didn't get any results until 24 hours later. So no corrective action was done at that time. There was such high flows which results in less contact time for the Sodium Hypochlorite. Another E coli test was done on 12-20-23 and the results were 0 colonies per 100mls sample. At the time the E coli was collected the flow was at 6.7 mg. The residual after the cloth filters was 1.29 Mg/l and the final in the pump was 0.0 Mg/l    
Stevens Brook Lake Champlain    
Marty Manahan Director of Public works    
   
   
nForms    
Y    
   
   
   
An E coli test was done on 12-18-23 on the combined final and bypass that was occurring because of the heavy rain. The test results were read today and we had an violation of 485 colonies per 100 mls sample. At the time when the E coli was collected the flow was at 13.8 mg. The CL2 residual on the Brigham road was 1.41 Mg/l and the final collected on the Kellogg road was 0.0 Mg/l.    
   
HQ0-0NJF-DMY73