Facility Name: St Albans City    
Brian Willett    
City of St.albans    
City plant    
06/11/2020    
06/11/2020    
11:06 am to 11:42 am    
   
Discharged partially treated disinfected effluent    
>10,000 to 100,000 gallons    
Pump Malfunction    
   
WWTF outfall    
I got the 3rd pump to reset and turn on and we were fine it dropped out of bypass.    
Stevens Brook Lake Champlain    
Marty Manahan    
   
   
nForms    
Y    
   
   
   
We had a rain storm and when the flow got up to the level to call for the 3rd primary effluent pump it did not turn on. We started bypassing at 5.7md instead of the 8.0mg that we are permitted at. We got locked out of the Scada screen for a bit and didn't realize what was going on. We got back on line and got The 3rd pump running. When I reported the incident on the web site i accidently reported it twice thinking the 1st one didn't go through.    
   