Waste Water Inventory Website
            Watershed Management Website Drinking Water Website Waste Management Website
View FacilityIncident Record


Facility Name: St Albans City    
brian willett chief operator    
city of stalbans    
stalbans wwtp    
06/22/2016    
06/22/2016    
10:00 am to 10:30 am    
   
Discharged partly treated undisinfected effluent    
>10,000 to 100,000 gallons    
Power Outage    
no obstruction    
WWTF outfall    
restored power to plant Electricians have traced the cause to the third pump in the WWTF pump station. On July 18th a soft start mechanism was installed for that pump to keep any further power outages from occuring. Repairs and upgrades have also been made to the generator / battery that runs the chemical feed for the chlorination system. this system will be checked weekly.    
Stevens brook that dumps in to lake cham    
Allen Robtoy Director of public works    
   
   
nForms    
Y    
   
   
   
Had a power outage for approx. 30 minutes due to some unknown electrical problem that kicked the main breaker off to the plant. power was restored within 30 mins. chemicals were not fed for approx. 20 mins. that chlorination and dechlorination.    
   
2GH-1QGQ-B9HY