Facility Name:
|
Middlebury
|
Caller Name And Title:
|
Jeremy Rathbun Wastewater Superintendent
|
Municipality:
|
Town of Middlebury
|
Location (street or site):
|
Treatment Plant
|
Incident Start Date:
|
05/31/2025
|
Incident End Date:
|
05/31/2025
|
Incident Start End Times:
|
08:30 pm to 09:00 pm
|
Estimated Duration Of Event:
|
|
Nature Of Incident:
|
Discharged partially treated disinfected effluent
|
Estimated Volume (gallons):
|
200000
|
Cause Of Discharge:
|
High Flows
|
Type Of Obstruction:
|
|
Point Of Discharge:
|
WWTF outfall
|
Corrective Action Taken:
|
The operators are modifying the control for Automated Storm Mode to try to prevent it from activating unless absolutely necessary. This will be done within the week.
|
Waterbody Impacted:
|
Otter Creek
|
Contact Name And Title For Public:
|
Jeremy Rathbun Wastewater Superintendent
|
Call Date:
|
|
WW Staff Called:
|
|
Type Of Notification:
|
nForms
|
Public Overflow Report For Web:
|
Y
|
|
|
|
|
|
|
Description Of Incident:
|
They Automated Wastewater Control System put the plant into storm mode. This resulted in flows beyond those designed for the plants UV disinfection system, and the possibility of partially treated discharge
|
|
|
nForm Submission Number:
|
HQD-1XWT-ZAK8Z
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|