Facility Name:
|
Essex Junction
|
|
|
James Jutras, Water Quality Supt. Chief Operator
|
|
|
Essex Junction
|
|
|
39 Cascade Street Wastewater Facility
|
|
|
03/16/2017
|
|
|
03/16/2017
|
|
|
06:15 pm to 09:10 pm
|
|
|
|
|
|
Discharged treated and partly disinfected effluent
|
|
|
>100,000 to 500,000 gallons
|
|
|
Other
|
|
|
N/A
|
|
|
WWTF outfall
|
|
|
made process adjustments, increased chemical feed set point and increased the rate of adjustment for automated feed systems.
|
|
|
Winooski River
|
|
|
James Jutras, Water Quality Supt, Chief Operator
|
|
|
|
|
|
|
|
|
nForms
|
|
|
Y
|
|
|
|
|
|
|
|
|
|
|
|
High Chemical Demand caused under disinfection of fully treated final effluent. E. Coli analysis 437 Colonies/100 ml at 0.49 mg/L total chlorine residual
|
|
|
|
|
|
HN3-DM1C-C0R68
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|