Facility Name: Brattleboro    
Josh Reitze    
Brattleboro    
Connecticut river at Brattleboro WWTP    
11/06/2024    
11/06/2024    
12:15 pm to 01:40 pm    
   
Discharged partially treated disinfected effluent    
1000000    
Unknown    
   
WWTF outfall    
Wastewater plant samples were tested in house and all results seem to be within our normal range. Resample was conducted on 11/6/24 to confirm if it is a fluke sample and results will be out tomorrow. Chlorine pumps turned up to keep range of residual at the top of allowable range. Re-sample was conducted on 11/6/24 came out with a result of 17.3 colonies which confirms it likely was a bad sample originally.    
Connecticut River    
Josh Reitze; Chief Operator    
   
   
nForms    
Y    
   
   
   
In house E.coli sample tested above the allowed 77 colonies per 100mL. Sample had normal chlorine residual that is used to meet treatment parameters on a normal basis.    
   