Facility Name:
|
Brattleboro
|
|
|
Josh Reitze, Chief Wastewater Operator
|
|
|
Brattleboro
|
|
|
Wastewater Treatment Plant
|
|
|
09/10/2024
|
|
|
09/11/2024
|
|
|
12:00 am to 12:00 pm
|
|
|
|
|
|
Discharged partly treated undisinfected effluent
|
|
|
500000
|
|
|
Chem Feed Problem
|
|
|
|
|
|
WWTF outfall
|
|
|
After the failed test was read, chlorine rate was adjusted and a new sample of the effluent was taken to check the E.coli level to see if the test happened to just be tainted. The sample from 9/11/24 resulted in a colony count 42.0 at 0.76 mg/L residual chlorine, which is within our permit limits of 77 colonies/100 mL.
Chlorine pump is being set up to keep a target of 0.75 mg/L or greater to ensure continued treatment. As well as flocculant pumps being turned up in rate to help solids settle easier due to the high water temperature and low flow rates.
|
|
|
Connecticut River South of WWTF
|
|
|
Josh Reitze; Chief Wastewater Operator
|
|
|
|
|
|
|
|
|
nForms
|
|
|
Y
|
|
|
|
|
|
|
|
|
|
|
|
Due to increase in retention time due to low flow, chlorine residual was being used up by the bacteria in water as well as the chlorine pumps were flowing at a very slow rate during this time period due to the low effluent discharge rate.
This resulted in a failed E.coli test that was sampled on Tuesday 9/10 with a test result of 2419.6 colony count.
|
|
|
|
|
|
HQ6-KBES-J49ZN
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|