Waste Water Inventory Website
GoTo=>             Watershed Management Website Drinking Water Website Waste Management Website
View FacilityIncident Record

Skip Navigation Links

Facility Name: Proctor    
Caller Name And Title: Christopher Hayes-Operator    
Municipality: Proctor    
Location (street or site): Stiles Meadow Pump Station    
Incident Start Date: 01/24/2019    
Incident End Date: 01/24/2019    
Incident Start End Times: 01:00 pm to 03:00 pm    
Estimated Duration Of Event:    
Nature Of Incident: Discharged untreated sewage    
Estimated Volume (gallons): >1,000 to 10,000 gallons    
Cause Of Discharge: High Flows    
Type Of Obstruction: No obstruction    
Point Of Discharge: Pump station emergency overflow pipe    
Corrective Action Taken: Pulled pump 2 for rebuild. Reset and had electrician confirm proper operation. Will monitor frequently until pump 2 is installed.    
Waterbody Impacted: Otter Creek    
Contact Name And Title For Public: Christopher Hayes    
Call Date:    
WW Staff Called:    
Type Of Notification: nForms    
Public Overflow Report For Web: Y    
   
   
   
Description Of Incident: Extremely high flows due to significant rain storm with snow melt. Stiles Meadow Pump Station collects gravity flow and receives water from another pumping station. Pump #2 Failed -motor. Pump #1 was barely keeping up with flow. Short to ground in pump 2 was causing the main power to trip also, interrupting pumping of 1.    
   
nForm Submission Number: HNM-2CFY-J8QQS