Facility Name:
|
Richmond
|
Caller Name And Title:
|
Brad Snow Assistant Superintendent
|
Municipality:
|
Richmond
|
Location (street or site):
|
Filters
|
Incident Start Date:
|
01/22/2025
|
Incident End Date:
|
01/22/2025
|
Incident Start End Times:
|
11:15 am to 12:15 pm
|
Estimated Duration Of Event:
|
|
Nature Of Incident:
|
Discharged partially treated disinfected effluent
|
Estimated Volume (gallons):
|
2900
|
Cause Of Discharge:
|
Other
|
Type Of Obstruction:
|
Order of Operations failure when swappin
|
Point Of Discharge:
|
WWTF outfall
|
Corrective Action Taken:
|
Once the problem was noticed by the team immediate action was taken. We initially started to swap back to the other tank because we didn't realize the belt wasn't turning because backwash was initated but then we realized and initiated the belt, and everything started to work fine.
|
Waterbody Impacted:
|
Winooski River
|
Contact Name And Title For Public:
|
Stephen Cote Superintendent
|
Call Date:
|
|
WW Staff Called:
|
|
Type Of Notification:
|
nForms
|
Public Overflow Report For Web:
|
Y
|
|
|
|
|
|
|
Description Of Incident:
|
Swapped filters and UV lights in the AM on 1/22/25 and the belt drive did not get initiated by the operator and overflowed the partially treated effluent through the UV lights and out to the Winooski River.
|
|
|
nForm Submission Number:
|
HQ9-V176-EVBXY
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|