Facility Name:
|
Bennington
|
|
|
Gail Tiffany - Lab Director
|
|
|
Bennington
|
|
|
244 Harrington Road
|
|
|
07/05/2016
|
|
|
07/06/2016
|
|
|
9:00 AM - 9:00 AM
|
|
|
24 hours
|
|
|
Discharged treated and partly disinfected effluent
|
|
|
2723000
|
|
|
Other
|
|
|
|
|
|
WWTF Outfall
|
|
|
Putting sand filter back into operation 7/7. Increased sodium hypochlorite feed 7/6. Will conduct additional sampling on 7/6.
|
|
|
Walloomsac River
|
|
|
Terrance Morse - Water Resources Superintendent
|
|
|
07/06/2016
|
|
|
Liz Dickson
|
|
|
E-Mail
|
|
|
Y
|
|
|
|
|
|
|
|
|
|
|
|
Failed RBC units recently put back into service and sloughing of older material may have contributed to high E. coli. E. coli. sample collected on 7/5 in excess of 11,000 colonies/100 ml.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|